The following tables list and describe the parameters specific to the UIS command component types for this remote device:
For more general information about UIS command component parameters, see UIS Command Components. The DG_F_DEV (Get data group from device) and DG_T_DEV (Send data group to device) command component types are configured in the template file. The other command component types are considered ‘special’ and are defined in the EIE editor code. See Special UIS Command Component Types for more information.
|
Update CygNet Point updates the record for a CygNet point. CYUPDTPT has the following command parameters:
|
|
Wait for CygNet Point signals the UIS to wait to perform a command until the value of the specified CygNet point changes to a specified value. CYWAITPT must be the first command component added to a UIS command. You cannot add other instances of CYWAITPT to a UIS command. CYWAITPT has the following command parameters:
|
Get data group from device retrieves a data group from a field device. The Parent XML Element is uccRecvParms. The following parameters are available for each specified data group type.
| Data Group Type | Parameter | Required | Description |
|---|---|---|---|
|
Cnt |
No |
Card Count defines the maximum number of card-type-specific instances readable from the selected "Dynagraph Card" (DynaCard) data group. Value options are integers from 1 to 30, depending on card type. |
|
|
Item |
No |
Custom Card ID defines the numeric ID of any of a number of AutoCom card types. See AutoCom documentation for a complete list of IDs, or see DynaCard data group custom card type options in the Choose Custom Card dialog box that appears when you click Get from RTU in the remote device editor. Value options are integers from 1 to 78, depending on card type. |
|
|
Num |
No |
Starting Card Number defines the index of a card type at which to begin reading card data. Value options are integers from 1 to 30, depending on card type. |
|
|
Cnt |
No |
Card Count defines the maximum number of card-type-specific instances readable from the selected "Dynagraph Card (Raw)" (DynaCardR) data group. Value options are integers from 1 to 10, depending on card type. |
|
|
Item |
No |
Custom Card ID defines the numeric ID of any of a number of AutoCom card types. See AutoCom documentation for a complete list of IDs, or see DynaCard data group custom card type options in the Choose Custom Card dialog box that appears when you click Get from RTU in the remote device editor. Value options are integers from 1 to 78, depending on card type. |
|
|
Num |
No |
Starting Card Number defines the index of a card type at which to begin reading card data. Value options are integers from 1 to 10, depending on card type. |
|
|
DataType |
Yes |
Data Type defines the type of data stored at the specified register number. Value options appear in the Data Type drop-down menu in the Single Register data group dialog box. |
|
|
Desc |
No |
Description | |
|
FacUdc |
No |
Facility.UDC for Point Processing provides a means to specify a UDC to which to map the specified data point; it requires a corresponding point in the Point Service (PNT). Value options are strings that specify a Facility.UDC combination. |
|
|
RegNum |
Yes |
Register Number specifies the register number used to retrieve data from a single element. Value options are valid register numbers. |
Send data group to device sends a data group to a field device. The parent XML Element is uccSendParms. The following parameters are available for each specified data group type.
| Data Group Type | Parameter | Required | Description |
|---|---|---|---|
|
DataType |
Yes |
Data Type defines the type of data stored at the specified register number. Value options appear in the Data Type drop-down menu in the Single Register data group dialog box. |
|
|
Desc |
No |
Description Value options are strings. |
|
|
FacUdc |
No |
Facility.UDC for Point Processing provides a means to specify a UDC to which to map the specified data point; it requires a corresponding point in the Point Service (PNT). Value options are strings that specify a Facility.UDC combination. |
|
|
RegNum |
Yes |
Register Number specifies the register number used to retrieve data from a single element. Value options are valid register numbers. |
|
|
Value |
Yes |
Value defines a value to be sent to the specified item. |